Primary & Secondary Fusion Pole mounted Circuit Breaker

Rated voltage 12KV
Rated current 630/1250A
rated frequency 50 Hz
peak withstand current 50/63 KA
Short-time withstand current 20/25 KA
short circuit closing current 50/63 KA
short-circuit breaking current 20/25 KA
Consult immediately
Detail

ZW32-12 type outdoor pillar vacuum circuit breaker (standard fusion type) fully complies with the State Grid's standardized design requirements for primary and secondary integrated overhead circuit breakers (pole type). It is primarily used in three-phase 12kV power systems with a 50Hz alternating current, serving as a segmentation and connection switch for 12kV power lines, as well as a boundary switch at the "T" joint of line users. It is paired with distribution automation terminals (FTUs) that meet the State Grid's standardization design specifications, capable of load breaking and making, handling overloads, short circuits, and providing protection for small current ground faults.Equipped with unified, standardized parameter current-voltage all-in-one sensors, the circuit breaker boasts a wide measurement range, high precision, and high reliability. It offers comprehensive analog signals and accurately identifies various types of line faults, ensuring comprehensive and precise protection functionality.

The circuit breaker canbe equipped with an integrated isolation switch(disconnector), which has a mechanical interlock to prevent mis-operation.


Application environment:


a.   Altitude:≤1000m;

b. The surrounding air temperature: -40℃~+40℃;Daily range of temperature:less than 25℃;

c. The ice thickness shall not exceed 10mm ;

d. The sunshine intensity is not greater than1000W/㎡;

e. The intensity of the earthquake does not exceed 8 degrees;

f. Free from inflammable, explosive, chemical corrosion and violent vibration;

g. The pollution level shall not exceed GB5582 level IV;


Main technical parameters


NO.

Item

unit

                  value

    1

Rated voltage

KV

                    12

    2

rated frequency

HZ

                    50

    3

Rated current

    A

                 630/1250

    4

Rated short-circuit breaking current

KA

                   20/25

    5

Rated peak withstand current (peak)

KA

                   50/63

    6

Rated short-time withstand current (4S)

KA

                   20/25

    7

Rated short circuit closing current (peak)

KA

                   50/63

    8

mechanical life

times

                   10000

    9

times of the rated short circuit closing current is broken

times

                      30

10

Rated operating sequence

    \

O—0.3s—CO—180s—CO

11

power frequency withstand voltage1min)wet) (dry) phase to phase,   ground/fracture

KV

                 30/42/48

12

Lightning impulse withstand current (peak) phase to   phase, ground/fracture

KV

                   75/85

13

secondary circuit 1min power frequency withstand   voltage

KV

                          2


Mechanicalcharacteristic parameter


No.

name of parameter

unit

data

          1

clearance between open contacts

mm

9±1

          2

Contact overtravel

mm

2.5±0.5

          3

opening speed

m/s

1.2±0.2

          4

closing speed

m/s

0.8±0.2

          5

Contact closing bounce time

ms

≤2

          6

Interphase center distance

mm

340±2

          7

Three phase switching and closing different period

ms

≤2

          8

Resistance of each phase conducting loop

μΩ

≤80(with disconnector≤140)

          9

closing time

ms

≤65

10

opening time

ms

≤45

11

Rated power of energy storage motor

W

40